5 x 10AWG

Description

Description

Standards

  • Product
    UL 1277; UL 83
  • National
    NTC 1332

Application

Low voltage secondary distribution. Indoor installations of industrial, comercial and residential buildings. Suitable for installation in cable tray.
 

Construction

Conductor
Soft copper conductor, class B, concentric stranded.

Insulation
Polyvinyl Chloride (PVC) and induvidual cover in nylon type THHN/THWN-2.

Jacket
Polyvinyl Chloride (PVC) outer sheath.

 

Specifications

Nexans's Power Cables THHN/THWN-2 are manufactured under the following standards:

  • ASTM B8, NTC 307.
  • ASTM B3, NTC 359.
  • UL 83, NTC 1332.
  • According to Retie and Norma 01864

Operating Temperature
90°C for wet and dry locations.

Operating Voltage
600V.

 

Marking

  • Insulation colors in yellow, blue, red, white and green.

Optional

  • Other configuration and conductor materials are available upon request.

Testing Conditions

  • Ampacity for 90°C conductor temperature, 30°C ambient temperature. No more than three current carrying conductors in a duct or raceway. NTC 2050, table 310-16.
  • Data indicated in this table are subject to normal manufacturing tolerances.

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulation
PVC/Nylon
Outer sheath
PVC
Conductor flexibility
Class B
Conductor shape
Compressed

Dimensional characteristics

Dimensional characteristics

Conductor diameter
2.85 mm
Conductor cross-section
5.26 mm²
Inner sheath thickness
0.1 mm
Average sheath thickness
1.52 mm
Approximate weight
428 kg/km
Conductor cross-section (AWG/KCMIL)
10 AWG
Nominal insulation thickness
0.51 mm
Nominal outer diameter
14.58 mm
Number of cores
5

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
3.485 Ohm/km
Operating voltage
600 V
Perm current rating in duct/buried 30°C
40 A

Mechanical characteristics

Mechanical characteristics

Abrasion resistance
High

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Oil resistance
Yes
U.V resistance
Yes

Fire safety characteristics

Fire safety characteristics

Fire retardant
Method 1 - Vertical Tray (UL 2556/9.6)

Resources

Resources

Selling & delivery Information

Packaging
Reels by 500m. or 1000m. +/- 5%

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close