SELF SUPPORTED MULTIPLEX CABLES 0.6/1kV (AAAC Neutral) - ENEL

Products

3x35+54.6

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Nominal insulation thickness: 1.6 mm
  • Approximate weight: 623.9 kg/km
  • Nominal outer diameter: 28.65 mm
  • Ampacity: 129.0 A
  • Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km

 

3x95+54.6

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Nominal insulation thickness: 1.8 mm
  • Approximate weight: 1187.6 kg/km
  • Nominal outer diameter: 40.26 mm
  • Ampacity: 253.0 A
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km

 

Description

Description

Application

SELF SUPPORTED MULTIPLEX CABLES Centelsa by Nexans are used in aerial secondary distribution systems, in public lighting or in temporary construction installations, connection with the transformer to the point of derivation for the user or connection with the distribution box.

Note: Any other application or use not described above is considered prohibited.

Construction

Phase Conductor

Aluminum 1350-H19 hard tempering, compact concentric stranded.

Neutral Conductor

Aluminum alloy 6201-T81 (AAAC) support conductor, concentric stranded.

Insulation

Composed of cross-linked polyethylene XLPE, resistant to UV rays.

Applicable standards

  • IEC 60228
  • GSCC 009 (ENEL)

Certificate

  • CIDET N° 07458
  • CIDET N° CP25_AA00631
  • CIDET N° CP25_AA00632

Operating Temperature

90 °C

Operating Voltage

0.6/1 kV

 

Identification

• Phase conductors identification by polarity traces.

 

Packaging units

Wooden reels in 500 o 1000 m.

Ampacity Conditions (Self Supported Multiplex Cables) ENEL

  • Ampacity to 90°C conductor temperature, 30°C ambient temperature.
  • For Methods F, Tree loaded conductors trefoil in free air according to IEC 60364-5.52, Table B.52.13.

NOTE:

  • The data reported here are nominal and are subject to tolerances according to standards and normal manufacturing practices.
  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Phase Conductor Type
AAC - All Aluminium Conductor
Conductor material
Aluminum Alloy 1350
Conductor flexibility
Class 2
Conductor shape
Compact stranded
Neutral Type
AAAC - All Alloy Aluminium Conductor
Insulation
XLPE

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Insulation thickness of neutral conductor
1.60 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Resistance of neutral conductor at 20ºC
0.63 Ohm/km

Mechanical characteristics

Mechanical characteristics

Rated breaking load
1769 kgf

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C
U.V resistance
Yes (720 hours)
RoHS compliant
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close