MULTICONDUCTOR POWER CABLE (AS+) FIRE RESISTANT 0.6/1kV

Products

5x2,5mm2

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Outer Diameter: 13.47 mm
  • Approximate weight: 259.8 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
  • Ampacity: 28.0 A

 

2x2,5mm2

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Outer Diameter: 10.72 mm
  • Approximate weight: 153.88 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
  • Ampacity: 28.0 A

 

3x2,5mm2

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Outer Diameter: 11.33 mm
  • Approximate weight: 179.98 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
  • Ampacity: 28.0 A

 

4x2,5mm2

Nexans ref.

  • Conductor cross-section: 2.5 mm²
  • Outer Diameter: 12.34 mm
  • Approximate weight: 215.15 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 7.98 Ohm/km
  • Ampacity: 28.0 A

 

5x4mm2

Nexans ref. 10040777

  • Conductor cross-section: 4 mm²
  • Outer Diameter: 14.95 mm
  • Approximate weight: 356.59 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
  • Ampacity: 36.0 A

 

2x4mm2

Nexans ref.

  • Conductor cross-section: 4 mm²
  • Outer Diameter: 11.82 mm
  • Approximate weight: 200.25 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
  • Ampacity: 36.0 A

 

3x4mm2

Nexans ref.

  • Conductor cross-section: 4 mm²
  • Outer Diameter: 12.51 mm
  • Approximate weight: 239.11 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
  • Ampacity: 36.0 A

 

4x4mm2

Nexans ref.

  • Conductor cross-section: 4 mm²
  • Outer Diameter: 13.67 mm
  • Approximate weight: 289.45 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 4.95 Ohm/km
  • Ampacity: 36.0 A

 

5x6mm2

Nexans ref. 10040447

  • Conductor cross-section: 6 mm²
  • Outer Diameter: 16.52 mm
  • Approximate weight: 465.46 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
  • Ampacity: 44.0 A

 

2x6mm2

Nexans ref.

  • Conductor cross-section: 6 mm²
  • Outer Diameter: 12.98 mm
  • Approximate weight: 255.74 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
  • Ampacity: 44.0 A

 

3x6mm2

Nexans ref.

  • Conductor cross-section: 6 mm²
  • Outer Diameter: 13.76 mm
  • Approximate weight: 310.36 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
  • Ampacity: 44.0 A

 

4x6mm2

Nexans ref.

  • Conductor cross-section: 6 mm²
  • Outer Diameter: 15.07 mm
  • Approximate weight: 379.16 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 3.3 Ohm/km
  • Ampacity: 44.0 A

 

5x10mm2

Nexans ref. 10040448

  • Conductor cross-section: 10 mm²
  • Outer Diameter: 19.19 mm
  • Approximate weight: 704.09 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
  • Ampacity: 58.0 A

 

2x10mm2

Nexans ref.

  • Conductor cross-section: 10 mm²
  • Outer Diameter: 14.96 mm
  • Approximate weight: 370.32 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
  • Ampacity: 58.0 A

 

3x10mm2

Nexans ref.

  • Conductor cross-section: 10 mm²
  • Outer Diameter: 15.9 mm
  • Approximate weight: 459.34 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
  • Ampacity: 58.0 A

 

4x10mm2

Nexans ref.

  • Conductor cross-section: 10 mm²
  • Outer Diameter: 17.46 mm
  • Approximate weight: 567.73 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
  • Ampacity: 58.0 A

 

5x16mm2

Nexans ref. 10040449

  • Conductor cross-section: 16 mm²
  • Outer Diameter: 21.6 mm
  • Approximate weight: 1002.93 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
  • Ampacity: 75.0 A

 

2x16mm2

Nexans ref.

  • Conductor cross-section: 16 mm²
  • Outer Diameter: 16.74 mm
  • Approximate weight: 512.9 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
  • Ampacity: 75.0 A

 

3x16mm2

Nexans ref.

  • Conductor cross-section: 16 mm²
  • Outer Diameter: 17.81 mm
  • Approximate weight: 649.86 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
  • Ampacity: 75.0 A

 

4x16mm2

Nexans ref.

  • Conductor cross-section: 16 mm²
  • Outer Diameter: 19.61 mm
  • Approximate weight: 811.77 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.7 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
  • Ampacity: 75.0 A

 

2x25mm2

Nexans ref.

  • Conductor cross-section: 25 mm²
  • Outer Diameter: 20.08 mm
  • Approximate weight: 758.82 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
  • Ampacity: 96.0 A

 

3x25mm2

Nexans ref.

  • Conductor cross-section: 25 mm²
  • Outer Diameter: 21.41 mm
  • Approximate weight: 968.23 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
  • Ampacity: 96.0 A

 

4x25mm2

Nexans ref.

  • Conductor cross-section: 25 mm²
  • Outer Diameter: 23.64 mm
  • Approximate weight: 1214.6 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
  • Ampacity: 96.0 A

 

5x25mm2

Nexans ref.

  • Conductor cross-section: 25 mm²
  • Outer Diameter: 26.11 mm
  • Approximate weight: 1511.58 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 0.78 Ohm/km
  • Ampacity: 96.0 A

 

2x35mm2

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Outer Diameter: 22.42 mm
  • Approximate weight: 1001.1 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
  • Ampacity: 115.0 A

 

3x35mm2

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Outer Diameter: 23.93 mm
  • Approximate weight: 1290.95 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
  • Ampacity: 115.0 A

 

4x35mm2

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Outer Diameter: 26.47 mm
  • Approximate weight: 1627.65 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
  • Ampacity: 115.0 A

 

5x35mm2

Nexans ref.

  • Conductor cross-section: 35 mm²
  • Outer Diameter: 29.27 mm
  • Approximate weight: 2029.34 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 0.9 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 0.554 Ohm/km
  • Ampacity: 115.0 A

 

2x50mm2

Nexans ref.

  • Conductor cross-section: 50 mm²
  • Outer Diameter: 25.82 mm
  • Approximate weight: 1376.63 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 1.0 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
  • Ampacity: 135.0 A

 

3x50mm2

Nexans ref.

  • Conductor cross-section: 50 mm²
  • Outer Diameter: 27.6 mm
  • Approximate weight: 1787.38 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 1.0 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
  • Ampacity: 135.0 A

 

4x50mm2

Nexans ref.

  • Conductor cross-section: 50 mm²
  • Outer Diameter: 30.57 mm
  • Approximate weight: 2261.21 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 1.0 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
  • Ampacity: 135.0 A

 

5x50mm2

Nexans ref.

  • Conductor cross-section: 50 mm²
  • Outer Diameter: 34.02 mm
  • Approximate weight: 2836.66 kg/km
  • Minimum outer sheath thickness: 1.32 mm
  • Nominal insulation thickness: 1.0 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 0.386 Ohm/km
  • Ampacity: 135.0 A

 

2x70mm2

Nexans ref.

  • Conductor cross-section: 70 mm²
  • Outer Diameter: 29.76 mm
  • Approximate weight: 1885.19 kg/km
  • Minimum outer sheath thickness: 1.24 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
  • Ampacity: 167.0 A

 

3x70mm2

Nexans ref.

  • Conductor cross-section: 70 mm²
  • Outer Diameter: 32 mm
  • Approximate weight: 2472.7 kg/km
  • Minimum outer sheath thickness: 1.32 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
  • Ampacity: 167.0 A

 

4x70mm2

Nexans ref.

  • Conductor cross-section: 70 mm²
  • Outer Diameter: 35.65 mm
  • Approximate weight: 3147.95 kg/km
  • Minimum outer sheath thickness: 1.4 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
  • Ampacity: 167.0 A

 

5x70mm2

Nexans ref.

  • Conductor cross-section: 70 mm²
  • Outer Diameter: 39.66 mm
  • Approximate weight: 3948.31 kg/km
  • Minimum outer sheath thickness: 1.48 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 0.272 Ohm/km
  • Ampacity: 167.0 A

 

2x95mm2

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Outer Diameter: 34.3 mm
  • Approximate weight: 2487.88 kg/km
  • Minimum outer sheath thickness: 1.32 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Ampacity: 197.0 A

 

3x95mm2

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Outer Diameter: 36.88 mm
  • Approximate weight: 3259.69 kg/km
  • Minimum outer sheath thickness: 1.4 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Ampacity: 197.0 A

 

4x95mm2

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Outer Diameter: 41.09 mm
  • Approximate weight: 4148.42 kg/km
  • Minimum outer sheath thickness: 1.48 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Ampacity: 197.0 A

 

5x95mm2

Nexans ref.

  • Conductor cross-section: 95 mm²
  • Outer Diameter: 48.82 mm
  • Approximate weight: 5534.79 kg/km
  • Minimum outer sheath thickness: 1.64 mm
  • Nominal insulation thickness: 1.1 mm
  • Number of cores: 5
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Ampacity: 197.0 A

 

2x120mm2

Nexans ref.

  • Conductor cross-section: 120 mm²
  • Outer Diameter: 38.5 mm
  • Approximate weight: 3132.58 kg/km
  • Minimum outer sheath thickness: 1.4 mm
  • Nominal insulation thickness: 1.2 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
  • Ampacity: 223.0 A

 

3x120mm2

Nexans ref.

  • Conductor cross-section: 120 mm²
  • Outer Diameter: 43.9 mm
  • Approximate weight: 4344.48 kg/km
  • Minimum outer sheath thickness: 1.48 mm
  • Nominal insulation thickness: 1.2 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
  • Ampacity: 223.0 A

 

4x120mm2

Nexans ref.

  • Conductor cross-section: 120 mm²
  • Outer Diameter: 49.21 mm
  • Approximate weight: 5554.02 kg/km
  • Minimum outer sheath thickness: 1.64 mm
  • Nominal insulation thickness: 1.2 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
  • Ampacity: 223.0 A

 

2x150mm2

Nexans ref.

  • Conductor cross-section: 150 mm²
  • Outer Diameter: 45.42 mm
  • Approximate weight: 4151.56 kg/km
  • Minimum outer sheath thickness: 1.56 mm
  • Nominal insulation thickness: 1.4 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
  • Ampacity: 251.0 A

 

3x150mm2

Nexans ref.

  • Conductor cross-section: 150 mm²
  • Outer Diameter: 49.05 mm
  • Approximate weight: 5425.85 kg/km
  • Minimum outer sheath thickness: 1.64 mm
  • Nominal insulation thickness: 1.4 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
  • Ampacity: 251.0 A

 

4x150mm2

Nexans ref.

  • Conductor cross-section: 150 mm²
  • Outer Diameter: 54.32 mm
  • Approximate weight: 6853.69 kg/km
  • Minimum outer sheath thickness: 1.72 mm
  • Nominal insulation thickness: 1.4 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
  • Ampacity: 251.0 A

 

2x185mm2

Nexans ref.

  • Conductor cross-section: 185 mm²
  • Outer Diameter: 50.18 mm
  • Approximate weight: 5055.79 kg/km
  • Minimum outer sheath thickness: 1.64 mm
  • Nominal insulation thickness: 1.6 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
  • Ampacity: 281.0 A

 

3x185mm2

Nexans ref.

  • Conductor cross-section: 185 mm²
  • Outer Diameter: 53.72 mm
  • Approximate weight: 6547.29 kg/km
  • Minimum outer sheath thickness: 1.72 mm
  • Nominal insulation thickness: 1.6 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
  • Ampacity: 281.0 A

 

4x185mm2

Nexans ref.

  • Conductor cross-section: 185 mm²
  • Outer Diameter: 59.69 mm
  • Approximate weight: 8297.97 kg/km
  • Minimum outer sheath thickness: 1.88 mm
  • Nominal insulation thickness: 1.6 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
  • Ampacity: 281.0 A

 

2x240mm2

Nexans ref.

  • Conductor cross-section: 240 mm²
  • Outer Diameter: 61.86 mm
  • Approximate weight: 6994.6 kg/km
  • Minimum outer sheath thickness: 1.8 mm
  • Nominal insulation thickness: 1.7 mm
  • Number of cores: 2
  • Max. DC resistance of the conductor at 20°C: 0.08 Ohm/km
  • Ampacity: 324.0 A

 

3x240mm2

Nexans ref.

  • Conductor cross-section: 240 mm²
  • Outer Diameter: 66.68 mm
  • Approximate weight: 8983.62 kg/km
  • Minimum outer sheath thickness: 1.88 mm
  • Nominal insulation thickness: 1.7 mm
  • Number of cores: 3
  • Max. DC resistance of the conductor at 20°C: 0.08 Ohm/km
  • Ampacity: 324.0 A

 

4x240mm2

Nexans ref.

  • Conductor cross-section: 240 mm²
  • Outer Diameter: 74.12 mm
  • Approximate weight: 11313.05 kg/km
  • Minimum outer sheath thickness: 2.04 mm
  • Nominal insulation thickness: 1.7 mm
  • Number of cores: 4
  • Max. DC resistance of the conductor at 20°C: 0.08 Ohm/km
  • Ampacity: 324.0 A

 

Description

Description

Standards

  • Product
    IEC 60502-1

Application

Secondary distribution in low voltage. Indoor installations of industrial, commercial and residential buildings that must continue to operate in case of exposure to fire. Suitable for installation in cable trays meeting the flame test according to IEC 60332-3-24 Category C and fire resistance test according to IEC 60331-21.

Fire Resistance Test (Circuit Integrity): The cable is subjected to direct flame exposure at a temperature of at least 750°C for a minimum of 90 minutes, followed by a 15-minute cooling period.

Throughout the test and cooling period, the cable must not experience short circuits or breaks in the circuit to which it is connected.

Construction

Soft copper conductor, flexible class 5 wiring, covered with flame retardant mica tape. 

Insulation

Cross-linked polyethylene (XLPE) compound.

Jacket

Halogen-free, low-smoke, flame retardant polyolefin compound (HFFR-LS).

Applicable Standards

IEC 60502-1.

Certificate

CIDET N°03475

Operating Voltage

0.6/1(1.2) kV

Identification

Insulation colors according to RETIE:

2 Conductors: Black-White

3 Conductors: Black-White-Green

4 Conductors: Black-White-Red-Green

5 Conductors: Yellow-Blue-Red-White-Green

Black Jacket.

Packaging Unit

500 m or 1000 m reels. Other packaging units available upon request.

Ampacity Conditions

  • IEC 60364-5-52, Table B.52.5, Method D1, Duct buried in the ground Ta: 20°C, Tc: 90°C.
  • The data indicated in this table are subject to normal manufacturing tolerances.

NOTE:

  • Other configurations not specified in this catalog may be available under special request and minimum manufacturing quantities.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Conductor flexibility
Class 5 IEC 60228
Conductor shape
Bunched Wires
Insulation
XLPE
Halogen free
Yes
Outer sheath
HFFR (Halogen Free Flame Retardant)

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Abrasion resistance
Good

Usage characteristics

Usage characteristics

Fire resistant
IEC 60331
Flame retardant
IEC 60332-3-24 Cat. C
Smoke density
IEC 61034-2
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close