TECK 90 600 V 3x2/0+1x6 AWG
TECK 90 600 V 3x2/0+1x6 AWG
Aplicación general como cable de energía en baja tensión.
Lee más- Nexans ref. : P00029829-2
Descripción
Descripción
Application:
General application in low voltage distribution networks in operating stations where high mechanical strength is required. The interlocked aluminum armour gives greater flexibility compared to the traditional steel armour and the type of conformation of the same make has a high resistance to loads that could be placed on it. Class I, Div.2 and Class II, Div.2 hazardous locations per NEC.
STANDARDS
PRODUCT
CSA C22.2 Nº 131-14; CSA C22.2 Nº 38-14
TEST
CSA C22.2 Nº 03-01; CSA C22.2 Nº 2556-15; CSA C22.2 N° 2556; UL 2556
CONSTRUCTION
1. Conductor: Soft copper, class B.
2. Insulation: Cross linked polyethylene XLPE.
3. Bare grounding conductor: Soft copper, class B.
4. Inner covering: Anti-flame compound polyvinyl chloride PVC.
5. Armour: Interlocked aluminum tape.
6. Outer sheath: Anti-flame compound polyvinyl chloride PVC.
MAIN CHARACTERISTICS
Resistance to abrasion and oils. Resistance to weather and sunlight. Its armour provides additional mechanical protection and provides greater flexibility compared with other types of armour. Does not propagate the FT-1 flame. Fire retardant according to C22.2 No 0.3-01/FT-4. Resistance to attack by rodents.
GAUGE
From 14 AWG up to 500 kcmil.
MARKING
For gauges equal to or smaller than 8 AWG:
INDECO BY NEXANS TECK90(XLPE) (Nb. cores x Gauge phase cond. + Gauge ground. cond.) 0,6 kV -25C FT1 FT4 SR CSA 255079 - Year - Sequential length.
For gauges higher than 8 AWG:
INDECO BY NEXANS TECK90(XLPE) (Nb. cores x Gauge phase cond. + Gauge ground. cond.) 0,6 kV -40C FT1 FT4 SR CSA 255079 - year - Sequential length.
PACKING
Non returnable wooden reels.
COLOUR
Insulation: See core identification.
Outer sheath: Black.
PRODUCT STANDARDS
CSA C22.2 Nº 131-14: Type TECK 90 cable.
CSA C22.2 Nº 38-14: Thermoset-insulated wires and cables.
TEST STANDARDS
CSA C22.2 N° 03-01: Test methods for electrical wires and cables.
CSA C22.2 N° 2556-15: Wire and cable test methods.
CSA C22.2 N° 2556: Wire and Cable Test Methods. Section 9.6: FT4 (Vertical-Specimen) Flame Test.
UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.
UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.
Calculation of Current Condition TECK 90
BASED ON CEC, PART 1, TABLE 2
Maximum conductor temperature: 90°C.
Ambient temperature: 30°C.
Características
Características
Características de construcción
Características de construcción
Características dimensionales
Características dimensionales
Características eléctricas
Características eléctricas
Características mecánicas
Características mecánicas
Características de uso
Características de uso
Nuestros sitios web
Selecciona tu país para conocer nuestros productos y soluciones
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania