FLEXIBLE COPPER XLPE/PVC

Products

CABLE CU 150 MM2

Nexans ref. 10048246

  • Approximate weight: 1599 kg/km
  • Average insulation thickness: 1.4 mm
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 16.96 mm
  • Nominal insulation thickness: 1.4 mm
  • Nominal outer diameter: 22.38 mm
  • Outer Diameter: 22.38 mm
  • Ampacity: 375.0 A
  • Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km

 

CABLE CU 240 MM2 XLPE/PVC

Nexans ref. 10048248

  • Approximate weight: 2360 kg/km
  • Average insulation thickness: 1.7 mm
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 20.94 mm
  • Nominal insulation thickness: 1.7 mm
  • Nominal outer diameter: 27.38 mm
  • Outer Diameter: 27.38 mm
  • Ampacity: 470.0 A
  • Max. DC resistance of the conductor at 20°C: 0.08 Ohm/km

 

Description

Description

Standards

  • Product
    HD 603; IEC 60502-1

Applications

General application as a power cable, in low voltage electrical distribution networks, industrial facilities, in buildings and switchgear stations. In fixed installations, in indoor and outdoor environments (in trays, gutters, staples). It can be installed in ducts or directly buried.

 

Construction

 

Conductor

Flexible soft copper.

 

Insulation

Cross-linked polyethylene XLPE.

 

Jacket

Polyvinyl chloride (PVC), flame retardant (FR) and UV resistant.

 

Applicable standards.

IEC 60502-1

UNE HD 603-1

 

Certificate

Used according to RETIE and STANDARD 

 

Operating temperature

90 ° C

Maximum overload temperature

130 ° C

Short circuit temperature

250 ° C

 

Operating voltage

ac = 0.6 / 1KV (Uo / U), 1.2Kv (Maximum value)

cc = 1.5KV, 1.8KV (maximum value)

 

Marking

NEXANS COLOMBIA. < Calibre mm2 > Cu FLEX XLPE/PVC CT 0.6/1KV 90C (M).

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Class 5
Conductor material
Copper class 5
Conductor shape
Compressed
Insulation
XLPE
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Abrasion resistance
Good

Usage characteristics

Usage characteristics

Rodent protection
No
U.V resistance
Yes

Resources

Resources

Selling & delivery Information

Packing
Reels by 500 or 1000m.+/-5%

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close