N2XSY 6/10 kV 400 mm2 PH25

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-2; IEC 60811-401; IEC 60811-402; IEC 60811-409; IEC 60811-501; IEC 60811-502; IEC 60811-504; IEC 60811-505; IEC 60811-506; IEC 60811-507; IEC 60811-508; IEC 60811-509
  • National
    ICEA S-93-639; NTP-IEC 60228; NTP-IEC 60502-2; UL 2556

Application

Power distribution in medium voltage. As transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations.

Construction

1. Conductor: Compact soft copper, class 2.

2. Inner semi-conductor: Tape and compound Extruded.

3. Insulation: Cross linked polyethylene XLPE-TR (Tree retardant).

4. External semi-conductor: Extruded strippable.

These last three components extruded CV (continuous vulcanization) triple extrusion in dry cure process.

5. Screen: Copper wires.

6. Tape: Polyester.

7. Outer sheath: Compound polyvinyl chloride PVC.

Main characteristics

Excellent properties against heat aging. Resistance to abrasion, moisture and sunlight. Adequate resistance to greases and oils. Flame retardant.

Cross section:

From 35 mm2 up to 500 mm2.

Marking:

INDECO S.A. N2XSY 6/10 kV - Section - PH (Screen section) - Year - Sequential length.

Packing:

Non returnable wooden reels.

Colour:

Insulation: Natural.

Outer sheath: Red.

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP-IEC 60502-2: Power cables with extruded insulation and their accessories for rated voltages from 6 kV up to 30 kV.

International standards

IEC 60228: Conductors of insulated cables.

IEC 60502-2: Power cables with extruded insulation and their accessories for rated voltages from 6 kV up to 30 kV.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.

IEC 60811-401: Thermal ageing methods. Ageing in an air oven.

IEC 60811-402: Water absorption tests.

IEC 60811-409: Loss of mass test for thermoplastic insulations and sheaths.

IEC 60811-501: Test for determining the mechanical properties.

IEC 60811-502: Shrinkage test for insulations.

IEC 60811-504: Bending test at low temperature for insulation and sheaths.

IEC 60811-505: Elongation at low temperature for insulations and sheaths.

IEC 60811-506: Impact test at low temperature for insulations and sheaths.

IEC 60811-507: Hot set test for cross-linked materials.

IEC 60811-508: Pressure test at high temperature for insulation and sheaths.

IEC 60811-509: Test for resistance of insulations and sheaths to cracking.

ICEA S-93-639: 5-46 kV Shielded Power Cable for Use in the Transmission and Distribution of Electric Energy. Section 9.4.2: Oil Immersion Test.

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.

Calculation of Current Condition Single-core M.V.

CALCULATION OF CURRENT CONDITION BASED ON NTP-IEC 60502-2 Annex B

Maximum conductor temperature: 90°C.
Ambient air temperature : 30°C.
Ground temperature : 20°C.
Depth of laying : 0,8 m.
Thermal resistivity of soil : 1,5 K.m/W.
Screens bonded at both ends.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Material of the inner semi-conductor
Extruded
Insulating material
XLPE-TR
Material of the external semi-conductor
Extruded strippable
Screen
Copper wires / 6mm²
Outer sheath
PVC
Sheath colour
Red
Lead free
Yes
Conductor flexibility
Class 2 IEC 60228
Conductor shape
Compact stranded

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
400 mm²
Screen section
25 mm²
Conductor diameter
23.1 mm
Diameter over insulation
30.9 mm
Diameter over screen
34.3 mm
Diameter over Sheath
38.1 mm
Approximate weight
4312 kg/km
Total number of wires
61

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
6 / 10 (12) kV
Max. DC resistance of the conductor at 20°C
0.047 Ohm/km
A.C. Conductor resist. at 90 °C - flat formation
0.0623 Ohm/km
A.C. Conductor resist. at 90 °C - trefoil formation
0.0648 Ohm/km
Dielectric strength core to screen AC
21.0 kV
Nominal capacitance
611.0 pF/m
Perm. current rating buried 20°C - flat formation
572 A
Perm. current rating in air 30°C - flat formation
938 A
Permissible short circuit current screen 0.5s
4.4 kA
Phase reactance 60 Hz - flat formation
0.1767 Ohm/km
Resistance of the screen
0.727 Ohm/km
Time of application Dielectric strength core to screen AC
5 min.
Voltage for partial discharge test
10.4 kV
Maximal partial discharge test
10 pC
Impulse voltage
75 kV
Phase reactance 60 Hz - trefoil formation
0.107 Ohm/km
Perm. current rating buried 20°C - trefoil formation
590 A
Perm. current rating in air 30°C - trefoil formation
845 A

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Class 2 IEC 60228

Usage characteristics

Usage characteristics

Oil resistance
ICEA S-93-639
Flame retardant
IEC 60332-1-2; FT1
U.V resistance
UL 2556 - Sunlight Resistance
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close